Boiler Steam Water Level Gauge

The Boiler Steam Water Level Gauge Model SEL indicates level status from the display equipment by identifying electric resistance of water and steam by electrode sensors. The level of water portion displays each level in green and the steam portion displays it in red on the indicator of the micro processor controller unit (MPU) installed at site and the remote indicator unit (RIU) in control room etc. A SEL-S series Level Switch installed on the drain port in the superheated steam line will detect the level of condensed water in the port.

– Detection of level and status for water and steam in boiler drums and steam generators
– For high temperature & pressure
– On site (local MPU) and remote (Computer or RIU) indicators
– 10 set point alarms, changeable
– Level gauge, transmitter, switch function in one device
– Battery backup (opt.)

download pdf datasheet

SKU: SEL Categories: ,
Description

Description

 The Boiler Steam & Water Level Gauge

steamwatergauge

The Boiler Steam Water Level Gauge Model SEL indicates level status from the display equipment by identifying electric resistance of water and steam by electrode sensors. The level of water portion displays each level in green and the steam portion displays it in red on the indicator of the micro processor controller unit (MPU) installed at site and the remote indicator unit (RIU) in control room etc. A SEL-S series Level Switch installed on the drain port in the superheated steam line will detect the level of condensed water in the port.

The detection part of the SEL-G series electrode type level gauge is composed of a water column and some electrode sensors.
The electrode sensors are installed to a water column, a device connected to a hight temperature/pressure vessel with different theral conductivity in fluids. The protection case is installed in order to avoid damage generated due to pressure eruption etc.

Max. Pressure: 300 kg/cm2
Max. Temperature 560°C

The Micro Processor Controller Unit MPU receives and handles liquid level and other signals received from the electronic sensor  at relevant position sets or installed position of the SEL-S series electrode type level switch through the micro processor unit (MPU)
This displays relevant alarm points on the MPU’s display window, together the color red on relevant LED’s on indicator with a maximum of 10 contact outputs for established alarm points.



Remote Monitoring Options

An indicator unit RIU for remote monitoring operation status of level gauge can be installed at the control room and being connected with MPU panel (max. 1,6 km).

The operational status and site situation of the level gauge can be monitored externally by a computer

Applications

  • Turbine water induction prevention.
  • Steam line drain control.
  • Boiler water high level protection.
  • Feedheater boiler low level protection.
  • Dearator level protection.